| MODEL |
UPS10000S |
UPS15000S |
UPS20000S |
UPS30000S |
| PHASE |
Three orders out |
| CABINET CAPACITY |
10000 VA / 8000 W |
15000 VA / 12000 W |
20000 VA / 16000 W |
30000 VA / 24000 W |
| INPUT |
|
|
| Nominal Voltage |
3 x 400 VAC (3Ph+N) |
| Voltage Range |
190-520 VAC (3 p h ) @ 50% load
305-520 VAC (3 p h ) @100% load |
|
46~54 Hz 56~64Hz |
| Frequency Range |
|
| OUTPUT |
|
| Nominal Voltage |
208/220/230/240VAC |
| Voltage Regulation |
± 1% |
| Frequency Range |
46~54 Hz @ 50Hz /56~64 Hz @ 60Hz |
| Frequency Range (battery mode) |
50 Hz ± 0.2 Hz o r 60 Hz ± 0.2 Hz |
| Current Crest Ratio |
3:1 |
| Harmonic Distortion |
≦ 3 % THD ( L i n e a r L o a d ) ; ≦ 5 % THD ( N o n l i n e a r l o a d ) |
| Transfer time |
ACmode to battery mode |
zero |
| Inverse to bypass |
zero |
|
|
| Waveform(batterymode) |
pure sinewave |
|
| EFFICIENCY |
|
|
91% |
93% |
91% |
| ACmodel |
| Batterymode |
91% |
87% |
88% |
| BATTERY |
|
|
Long-run model |
Batterytype |
It depends on the applicant |
| Numbers |
16PCS |
20PCS |
16PCS |
20PCS |
16PCS |
20PCS |
16PCS |
| Chargingcurrent(max) |
preinstall 4A, 1A/2A/4A (adjustable) |
12A |
| Chargingvoltage |
218.4 VDC ± 1% |
273 VDC ± 1% |
218.4 VDC ± 1% |
273 VDC ± 1% |
218.4 VDC ± 1% |
273 VDC ± 1% |
218.4 VDC ± 1% |
| INDICATORS |
|
| LCD |
Loadsize,Batterycapacity,ACmode,Batterymode,Bypassmode, andFaultindication
|
| ALARM |
|
| BatteryMode |
Sounding every 4 seconds
|
|
| LowBattery |
Sounding every seconds
|
|
| Overload |
Sounding twice every seconds
|
|
| Fault |
Continuously sounding
|
| PHYSICAL |
|
| Long-run |
Dimension,DxWxH(mm) |
442 x 190 x 318
|
575 x 190 x 318 |
815 x 250 x 826 |
| model |
Netweight (kg) |
15 |
16 |
22 |
64 |
| ENVIRONMENT |
|
| Humidity |
0-95% RH@ 0-40°C (Non-condensation)
|
| Nosise Level |
Lessthan60 dBA@ 1 m
|
| MANAGEMENT |
|
|
| SmartRS-232 /USB |
Windows®2000/2003/XP/Vista/2008,Windows®7/8, Unix and MAC
|
|
| OptionalSNMP |
PowermanagementfromSNMP manager andweb browser
|
|
|