TECHNICAL SPECIFICATION
MODEL |
UPS1000L |
UPS2000L |
UPS3000L |
UPS6000L |
UPS 10000L |
PHASE |
Single hand to hand |
CAPACITY |
1000 VA / 800 W |
2000 VA / 1600 W |
3000 VA / 2400 W |
6000VA/4800W |
10000VA/800W |
INPUT |
Nominal Voltage |
200/208/220/230/240VA |
208/220/230/240VAC |
Input Voltage Range |
110 -300VAC or 50% load ; 160 -280 VAC or 100% load |
110 -300VAC or 50% load ; 176-300 VAC or 100% load |
Frequency Range |
40Hz ~70Hz |
46~54Hz or 56~64Hz |
Power Factor |
(100% load) ≧0.99
|
OUTPUT |
Output Voltage |
200/208/220/230/240VAC |
208/220/230/240VAC |
Voltage Regulation |
± 1%
|
Frequency Range (Synchronized Range) |
47-53Hz or 57-63Hz |
46-54Hz or 56-64Hz |
Frequency Range (Batt. Mode) |
50Hz±0.25Hz or 60Hz±0.3Hz |
50 Hz or 60Hz ± 0.1 Hz |
Current Crest Ratio |
3:1
|
Harmonic Distortion |
≦ 3 % THD (Linear Load)
≦ 6 % THD (Non-linear Load) |
≦ 3 % THD (Linear Load)
≦ 5 % THD (Non-linear Load) |
Transfer Time |
AC to DC |
Zero
|
Inverter to Bypass |
4 ms (Typical) |
Zero |
Wave Form (Batt. Mode) |
Pure Sine wave
|
EFFICIENCY |
To AC Mode |
88% |
89% |
90% |
92% |
93% |
To Battery Mode |
83% |
87% |
88% |
90% |
91% |
BATTERY |
Standard Model |
Battery Type |
12V/9AH/7AH
|
Numbers |
2 |
4 |
6 |
16 |
16 |
Charging Current (max.) |
1 A |
1A/2A |
Charging Voltage |
27.4VDC ± 1% |
54.7 VDC ±1% |
82.1 VDC ±1% |
218.4 VDC ±1% |
Long-run Model* |
Battery Type |
Depending on the capacity of external batteries
|
Numbers |
3 |
6 |
8 |
16 ~ 20 ( A d j u s t a b l e ) |
Charging Current (max.) |
1A/2A/4A/6A (Adjustable) |
1A/2A/4A/6A ( A d j u s t a b l e , 6A i s only available for16pcs batteries |
Charging Voltage |
41.0VDC ± 1% |
82.1 VDC ±1% |
109.4VDC ±1% |
218.4 VDC ±1% |
273VDC ± 1% |
218.4VDC ± 1% |
273VDC ± 1% |
INDICATORS |
LCD |
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
|
ALARM |
Battery Mode |
Sounding every 4 seconds
|
Low Battery |
Sounding every second
|
Overload |
Sounding twice every second
|
Fault |
Continously sounding
|
PHYSICAL |
Standard Model |
Dimension, D x W x H (mm) |
282*145*220 |
397*145*220 |
369*190*318 |
442*190*688 |
Net Weight (kgs) |
8.7 |
15.7 |
24.6 |
61 |
66 |
Long-run Model* |
Dimension, D x W x H (mm) |
282*145*220 |
397*145*240 |
369*190*318 |
442*190*318 |
Net Weight (kgs) |
4.1 |
6.8 |
7.4 |
12 |
16 |
ENVIRONMENT |
Humidity |
20-90 % RH @ 0- 40°C (non-condensing) |
0-95% RH@0-40°C (non-condensing) |
Noise Level |
Less than 50 DB@ 1 m |
Less than 55 DB @ 1 m |
Less than 58 dBA @ 1 m
|
MANAGEMENT |
Smart RS-232/USB |
Windows ® 2000/2003/XP/Vista/2008,Windows® 7/8, Unix and MAC
|
Optional SNMP |
Power management from SNMP manager and web browser
|
When 1-3L UPS is set to constant voltage and constant frequency mode, the output power will drop by 20%, and when the output voltage of the UPS is set to 208VAC, the output
power will drop by 20%.
When 6 / 10L UPS is set to constant voltage and constant frequency mode, the output power drops by 40%, and when the output voltage of the UPS is set to 208VAC, the output
power amount drops by 10%.* * When the number of internal batteries e machine will derate the output according to the following formula: P=Prating X (N / 20 x 100%).
If the machine is installed above 1000 meters, every 100M increases.
Changes in the current product specifications will not be notified separately